Modbus TCP — Protocol Basics

How Modbus TCP works, frame structure, register types and your first connection to an industrial device.

modbusindustrialnetworkingpython

What is Modbus?

Modbus is a communication protocol developed in 1979 by Modicon. Despite its age, it remains the most widely used protocol in industrial automation — you'll find it in PLCs, drives, energy meters, temperature sensors and dozens of other devices.

Two main variants exist:

  • Modbus RTU — serial communication (RS-485), binary encoding
  • Modbus TCP — Modbus wrapped in TCP/IP, port 502

Modbus TCP Frame Structure

Each Modbus TCP frame consists of two parts:

MBAP Header (7 bytes)

[Transaction ID: 2B] [Protocol ID: 2B] [Length: 2B] [Unit ID: 1B]
  • Transaction ID — request/response pair, set by client
  • Protocol ID — always 0x0000 for Modbus
  • Length — number of following bytes
  • Unit ID — device address (like address in RTU)

PDU — Protocol Data Unit

[Function Code: 1B] [Data: N bytes]

Register Types

Type Address Size Access
Coil 00001–09999 1 bit R/W
Discrete Input 10001–19999 1 bit R
Input Register 30001–39999 16 bit R
Holding Register 40001–49999 16 bit R/W

Holding Registers (FC 03) are the most commonly used — devices store process values there.

First Connection in Python

from pymodbus.client import ModbusTcpClient

client = ModbusTcpClient(host="192.168.1.10", port=502)
client.connect()

# Read 10 registers from address 0, unit ID = 1
result = client.read_holding_registers(address=0, count=10, slave=1)

if not result.isError():
    print(result.registers)  # list of int values

client.close()

Common Pitfalls

  1. Addressing — in device docs, address 40001 is register 0 in FC03. Always subtract 40001.
  2. Endianness — 32-bit values (float, dword) are composed of two registers, byte order varies. Check the manual.
  3. Timeout — pymodbus default is 3s. Increase for slow industrial networks.